Construction Specifications
Structural design for ecobrick is performed to the requirements of the Australian Standard AS3700 ‘Masonry Code’.
The following tables have been prepared from AS3700 as a guide to the dimensions of internal partition walls not subject to wind loading.
All structural assessments of the suitability of ecobrick should be carried out by a suitably qualified engineer.
1. Single leaf 90mm thick ecobrick wall.
| Maximum Height (m) | Maximum length to next intersecting wall (m) |
|---|---|
| 2.4 2.8 3.0 3.2 3.5 |
6.0 4.0 3.0 2.5 2.0 |
2. Double leaf 230mm thick ecobrick wall (90mm, 50mm cavity, 90mm) joined with suitable cavity ties.
| Maximum Height (m) | Maximum length to next intersecting wall (m) |
|---|---|
| 5.0 6.0 6.5 7.0 |
6.0 5.5 4.0 3.5 |